Wire Gauge Calculator - AWG Size, Ampacity & Voltage Drop (NEC)

🔍 搜尋計算器

輸入關鍵字快速找到你需要的工具,支援模糊搜尋

Usage Notes & Disclaimer
Safe

Recommended Wire Gauge

AWG 12
(≈ 3.31 mm²)
Actual Voltage Drop 5.14 V (2.14%)
Ampacity (75°C) 25 A
Power Loss 67 W
Wire Resistance 0.395 Ω
Recommended EMT Size 1/2" EMT
Recommended Breaker 15A (2P)

💡 Practical Recommendation

Recommended actual size:

AWG 10

Upsize one gauge for ~30% headroom for future loads

Voltage Drop Analysis

Next Step

Whole-home load calc Estimate this device cost

Input Parameters

Templates are typical values for reference only. Always use the actual nameplate rating.
Range: 100-50000 W
Range: 1-200 A
Range: 1-300 ft
Advanced (voltage drop / wiring / temperature / conductor count / continuous load)
Range: 1-10 %
Range: 30-60 °C (86-140 °F)

Shortcut: Ctrl+S Save

Wire Ampacity Chart (NEC 310.16)

Data source: NEC Table 310.16, copper conductors. Ampacity shown for 60°C / 75°C / 90°C insulation at 30°C (86°F) ambient, ≤3 current-carrying conductors. Sizing here uses the 75°C column; small conductors (14/12/10 AWG) are limited by NEC 240.4(D) to 15/20/30 A breakers.

AWG 60°C (A) 75°C (A) 90°C (A) Circular Mils Notes
141520254,11015A max breaker
122025306,53020A max breaker
1030354010,38030A max breaker
840505516,510
655657526,240
470859541,740
38510011552,620
29511513066,360
111013014583,690
1/0125150170105,600
2/0145175195133,100
3/0165200225167,800
4/0195230260211,600
250 kcmil215255290250,000
300 kcmil240285320300,000
350 kcmil260310350350,000
EMT Conduit Fill Reference (NEC Chapter 9)

Maximum copper THHN/THWN-2 conductors per EMT trade size at 40% fill (NEC Chapter 9, Tables 1, 4 & 5). For 3 or more conductors the fill limit is 40%.

EMT Trade Size 40% Fill Area (in²) #12 THHN #10 THHN #8 THHN #6 THHN
1/2"0.1229532
3/4"0.213161054
1"0.346261696
1-1/4"0.59844281611
1-1/2"0.81461382216
2"1.342100633626

Tip: These are code maximums at 40% fill. Upsize the conduit one trade size for easier pulling and future adds.

⚠️ Safety Reminders

  • Reference data only. Actual installation must comply with the current NEC and local code
  • All electrical work should be performed by a licensed electrician
  • Ambient temperature, wiring method, and conductor count all affect ampacity
  • Reserve a 20-30% safety margin
About / How to use / Formulas / FAQ / Example

About This Wire Gauge Calculator

What is Wire Gauge Sizing?

Wire gauge sizing determines the correct copper conductor (AWG) for a circuit based on the load current, the run length, and the allowable voltage drop. Sizing to the NEC (NFPA 70) keeps the conductor within its safe ampacity so it does not overheat, and keeps voltage drop low enough that equipment runs properly - while avoiding the cost of oversized wire.

How to Use This Calculator

  1. Enter the load current: read the nameplate, or calculate it from power ÷ voltage (I = P / V)
  2. Enter the wire length: the one-way distance from the panel to the load, in feet
  3. Select the voltage: 120V or 240V single-phase, or 208V / 480V three-phase
  4. Set the allowable voltage drop: NEC recommends ≤3% on a branch circuit, ≤5% total
  5. Choose the wiring method: raceway/cable per NEC Table 310.16
  6. Set the ambient temperature: hot locations derate ampacity
  7. Read the recommended AWG, breaker size, and EMT conduit

Calculation Formulas

1. Voltage Drop (NEC Chapter 9 method)

Single Phase: VD = (2 × K × I × L) / CM

Three Phase: VD = (1.732 × K × I × L) / CM

Where K = 12.9 (copper resistivity constant, Ω·cmil/ft at 75°C), I = current (A), L = one-way length (ft), CM = conductor circular mils. This resistance-only method ignores conductor reactance and power factor; for long runs, large conductors, or low-PF/inductive loads (motors, compressors), the real voltage drop is higher - use the full impedance method. Ampacity follows NEC Table 310.16, breakers NEC 240.6 / 240.4(D), and conduit fill NEC Chapter 9.

2. Voltage Drop Percentage

Voltage Drop (%) = (VD / nominal voltage) × 100%

3. Power Loss

Power Loss (W) = I² × R (round trip)

FAQ

Q1: Why can't voltage drop be too large?

Excessive voltage drop causes: (1) low voltage at the equipment, so it may not run correctly (2) dim lighting (3) hard motor starting or overheating (4) wasted energy as heat. The NEC recommends keeping voltage drop to ≤3% on a branch circuit and ≤5% for branch + feeder combined (NEC 210.19 and 215.2 informational notes).

Q2: What is ampacity?

Ampacity is the maximum current a conductor can carry continuously without exceeding the temperature rating of its insulation. Exceeding it overheats the wire, degrades the insulation, and can start a fire. Ampacity comes from NEC Table 310.16 and is derated for ambient temperature (310.15(B)(1)) and for more than three current-carrying conductors (310.15(C)(1)).

Q3: What do AWG numbers mean?

AWG (American Wire Gauge) is the US standard for wire size. The scale is inverse: a smaller AWG number means a thicker (higher-ampacity) wire. Below AWG 1 the sizes continue as 1/0, 2/0, 3/0, 4/0, then kcmil (thousands of circular mils). Example: 14 AWG (15A) < 12 AWG (20A) < 10 AWG (30A) < 8 AWG (50A).

Q4: Why is temperature correction needed?

Table 310.16 ampacity is based on a 30°C (86°F) ambient. When the surroundings are hotter, the conductor cannot shed heat as well, so its allowable current is reduced (derated). For example, at 40°C (104°F) the 75°C-column factor is 0.88, so ampacity drops to about 88% of the table value.

Q5: What matters during the actual installation?

1. Follow the current NEC and any local amendments 2. Use a licensed electrician 3. Confirm the equipment nameplate rating 4. Account for continuous loads at 125% 5. Derate for high ambient temperature and for more than three conductors in a raceway 6. Verify terminal temperature ratings (60°C vs 75°C).

Usage Example

Example: 240V Appliance Circuit

  • Load: 30 A appliance / subpanel feeder
  • Distance: 80 ft from the panel
  • Voltage: 240V single-phase
  • Allowable voltage drop: 3%
  • Wiring: copper in EMT, 3 conductors
  • Result: 10 AWG copper, actual voltage drop ~2.5%, 30 A breaker, 1/2" EMT - meets NEC ampacity and voltage-drop limits with margin.
}
語言 (Language)
繁體中文
English
問題回報
加入收藏